HC PVE : Comparisons between Induction and Impulse systems

 

Comparisons between Ducting,
Induction and Impulse systems
Induction System Facts and Fiction!
Advantage over Impulse
Opportunity of a lower car park build height
'Fact' Only using modern Induction system
( use of induction fans can save over 600mm of excavation over a 3 story car park )
Yes
Induction systems offer a large saving in cable length and cost
'Fact' Induction systems use approx 60% less fans therefore 60% less cable
Yes
Induction systems use less cable trays and reduced fixing time
'Fact' Induction systems use less cable = less fixing time =lower cost,
Yes
Induction systems use less fans / Less Maintenance cost
'Fact' Induction systems use less fans = faster and more cost effective maintenance
Yes
Induction systems have adverse effect on sprinkler patterns
'False' Under test Induction fan discharge arrangement offers far superior and more reliable flow pattern over sprinklers.
Yes
Reduced size and cost of main control panel.
'Fact' Induction systems use less fans meaning less contactors = smaller panel size
Yes
Better to use larger quantity of Impulse fans than lower number of Induction fans
'Totally False' Unless you are a fan manufacturer!
Its been said!
Impulse fans can be installed as direct alternatives to induction fans

'False' Induction fans give over 3 times the performance of Impulse Fans. Using as direct replacements would seriously

'affect the fire stratagy and put at risk the well being of fire service personnel.

Yes
Induction fans largely unaffected by down stand beams
'Fact' Unlike impulse fans, induction fans discharge at a fixed angle for optimum flow. Fans can be mounted within 0.5m of downstand beam and need no room behind fan as air is pulled directly from below.
Yes
Smaller space requirement for control gear
'Fact' Induction systems use smaller control panels = smaller space requirement .
Yes
Smaller diameter Impulse fans can be used to offset lower floor to soffit heights.
'False' Using smaller impulse fans results in a dramatic rise in the quantity of fans required to move the same air.
( 1off induction = 3off 400 dia impulse fans = 6 off 315 dia impulse fans )
Yes
Induction systems offer a large reduction in consumed power
'Fact' lower number of fans = lower consummed power
typical example ( 3 x induction @1.2kw = 3.6kw . 9 x impulse @1.1kw = 9.9kw )
Yes
Induction systems require smaller battery back up and generator size.
'Fact' Lower power requirement = lower generator KVA rating
Yes
Induction fan design means correct thrust determined on site
'Fact' Variable speed motors on all induction fans
Yes
Impulse systems offer lower system losses with less jetstream contact with soffit
False ' Under test this proved to be simply rubbish .
N/A
Axial impulse fans have superior performance
'False' The modern day Induction fan offers a far superior system with far better performance .
( The above statement by Hans Speulman inventor of both impulse and 12 years later the induction system )
Yes
Mounting fans above car lane gives optimum system performance
'Fact' It is moving cars that produce CO therefore air movement should occur down driving lanes not over parked vehicle.
Yes
Induction systems can force smoke into escape routes
'False' Correct system design should ensure a comparible flow rate for Induction or Impulse systems
Same advantage
Induction is commercially and financially a more modern and sustainable system.
'Fact' Induction systems use less raw material and consume less power both issues lead to a more sustainable system.
Yes
Thrust systems eliminate the need for ducting.
'Fact' Both Induction and the less effective Impulse systems eliminate the need for ducting
Same advantage
Impulse fans are quieter than induction fans
Both fan types are designed to and do operate at around 50dBA within the car park .
Same advantage
Induction fans produce more thrust
'True' Induction fans are centrifugal based and currently produce up to 100N of thrust
( max trust of typical 400 impulse fan 40N or 315 impulse 12N )
Yes
Induction fans induce more air
'True' Induction fans induce 18 times the amount of air passing through the fan at 50m.
( impulse fans induce 8 times the amount of air at 12m )
Yes
Thrust systems offer vastly reduced system resistance means reduced power demands.
Both systems use thrust ventilation principal therefore no ducting resistance
Same advantage
Thrust systems offer a cleaner car park environment.
Both systems offer a cleaner car park environment
Same advantage
Thrust systems offer lighter, fresher, more welcoming atmosphere within the facility.
Both systems offer car parks that have a fresher more welcoming environment
Same advantage
Thrust systems offer safer environment for users.
Both systems are more open and thus safer for users
Same advantage
Thrust systems offer early fire detection means less likelihood of building structural damage.
Both systems should offer a high density of multi criteria fire detectors ( 1 off every 60m2)
Same advantage
Thrust systems offer greater safety for attending fire services.
Moving large quantities of air over the fire souce creates greater visability for the attending services.
Same advantage
Thrust systems offer more reliable and effective smoke extraction and control
Thrust systems are less prone to damage and create a controlled flow of smoke to the extraction point.
Same advantage
Thrust systems offer lower noise levels throughout the car cark.
Thrust systems are demand driven and operate at the exact demands for a given condition
( noise levels should only be high under a fire condition )
Same advantage
Induction systems are dangerous for toupe wearers
'False' in over 1000 installation worldwide HC Group have never had a problem of this type.
Its been said !!
Thrust systems offer better space optimisation (often creating more spaces)
Thrust systems do not use ducting therefore more space available within the car park.
Same advantage
Thrust systems offer vastly reduced day-to-day running costs.
Thrust systems are demand driven if system calls for 3 ac/h the fans will only operate at the required duty.
Same advantage
Thrust systems offer potentially lower insurance premiums to the car park owner.
Safer more open car parks mean less potential danger to occupants therefore lower Insurance premiums
Same advantage
Induction fans could be dangerous to people carrying long sticks
'False' as above in over 1000 installations we have never had a problem of this type.
Its also been said !!!
Induction systems offer easier and less disruptive installation.
'Fact' Induction systems use les fans less cabling and can be installed faster than impulse systems at lower cost.
Yes
Thrust systems are more flexible and reliable.
'Fact' Both Induction and the older impulse system are more flexible and reliable than ducted systems.
Same advantage